Loading...

The FBS range provides a compact, adaptable solution for supporting flat copper conductors in low-voltage distribution assemblies.

Built from high-strength glass-reinforced polyamide 6.6, each busbar support achieves Icw fault ratings up to 50 kA for 1 s.

Its modular, stackable design lets engineers combine top and bottom sections to achieve the required conductor spacing and configuration.

This flexibility makes FBS busbar supports ideal where multiple conductor sizes or layouts are used, helping reduce component counts while maintaining safe electrical separation and reliable mechanical performance.

Need help specifying the right components?

Key Features

  • Icw fault rating: up to 50 kA for 1 s
  • Conductor range: 3-10 mm thickness (flat bars)
  • Modular design: stackable top and bottom units
  • Voltage rating: Ue / Ui 1000 V AC, 1500 V DC
  • Impulse withstand: 12 kV
  • Material: Glass-reinforced polyamide 6.6
  • Continuous conductor temperature: 120 °C (max 125 °C)
  • Flammability: UL 94 V-0, Glow wire 960 °C

Need a bespoke solution?

Our compression & injection moulding expertise allows us to design & manufacture tailored components to your specification.

Technical Information for FBS Range Busbar Supports

You will find useful technical information below but, if you have any questions, please contact our technical team for support.

3D Render, cropped of the
  • Flammability: UL 94 V-0
  • Glow Wire: 960 °C
  • Equipment Voltage Ue: 1000 V AC, 1500 V DC
  • Insulation Voltage Ui: 1000 V AC, 1500 V DC
  • Impulse Voltage Uimp: 12 kV

† In line with the requirements set out in IEC 61439, FBS supports are capable of carrying conductors operating at an average of 120 °C (max. 125 °C), the material for the supports having a satisfactory thermal index value established using methods similar to IEC 60216.

Part Number3D ModelFBS PositionWidth Across FlatsWidth Across Corners
FBS3-10TFBS3-10T STEP fileTop50 mm57.7 mm
FBS3-10BFBS3-10B STEP fileBottom50 mm57.7 mm
ConductorsSupport SpacingTermate Icw RatingDuration
1 × 75×10 mm300 mm50 kA1 s
1 × 50×10 mm300 mm50 kA1 s
2 × 50×10 mm300 mm50 kA1 s
1 × 50×10 mm450 mm36 kA1 s
1 × 50×10 mm450 mm50 kA100 ms
1 × 30×3 mm300 mm36 kA100 ms
1 × 25×10 mm300 mm36 kA1 s
1 × 25×10 mm300 mm50 kA100 ms
1 × 25×10 mm450 mm36 kA1 s
Diagrams showing typical installations of the FBS Range for conductor sizes of 3, 5, 6/6.3, 8, and 10

M10 bolts recommended tightening torque 24Nm

38

Termate is committed to the highest standard of customer focus and we have made every effort to maintain the accuracy and completeness of the information provided in this data.

Where improvements to our products affect their installation and usage we endeavour to contact any customers who may be affected.

Warranty as stated in our Terms and Conditions of Trading is void if any modification is made to the warranted product.

Contact Us Today