MX Range Busbar Supports
Multi-phase supports for flexible panel layouts
The MX range provides a versatile, fixed-configuration solution for supporting conductors across a wide variety of panel designs.
Available in both three-phase and three-phase + neutral versions, these supports achieve Icw fault ratings up to 65 kA for 3 s.
Their consistent geometry and robust glass-reinforced polyamide 6.6 construction make them ideal for standardising designs across multiple assemblies.
Metric and imperial options suit both bare and insulated copper conductors, while different phase centres and bar configurations allow easy integration into new or retrofit installations.

Need help specifying the right components?

Key Features
UL Recognised Component
(Files E505645 (US) and E505645 (CA))- Icw fault rating: up to 65 kA for 3 s
- Configurations: 3-phase or 3-phase + neutral
Conductor options: bare or insulated copper, metric & imperial
- Phase centres: 60-110 mm with multiple bar configurations
Voltage ratings: up to 1000 V AC/DC
Impulse withstand: up to 12 kV
- Material: glass-reinforced polyamide 6.6
- Continuous conductor temperature: 140 °C (max 145 °C)
- Flammability: UL 94 V-0, Glow wire 960 °C
Need a bespoke solution?
Our compression & injection moulding expertise allows us to design & manufacture tailored components to your specification.
Technical Information for MX Range Busbar Supports
You will find useful technical information below but, if you have any questions, please contact our technical team for support.

- Material: Glass Reinforced Polyamide 6.6
- Conductor Temp.: 140 °C†
- Flammability: UL 94 V-0
- Glow Wire: 960 °C
- Equipment Voltage, Ue: 1000 V AC, 1500 V DC
- Insulation Voltage, Ui: 1000 V AC, 1500 V DC
- Impulse Voltage, Uimp: 12 kV
UL Recognised Component:
(Files E505645 (US) and E505645 (CA))
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085.
Reference
| Part Number | 3D Model | Number of Phases | Conductor Width (mm) | Phase Centres | Bars Per Phase | Termate Icw Rating |
|---|---|---|---|---|---|---|
| MXM6013NS | MXM6013NS STEP file | 3 | 10 | 60 | 1 | 50 kA 1 s |
| MXM6513NS | MXM6513NS STEP file | 3 | 10 | 65 | 1 | 50 kA 1 s |
| MXM8213NS | MXM8213NS STEP file | 3 | 10 | 82 | 1 | 65 kA 3 s |
| MXM8223NS | MXM8223NS STEP file | 3 | 10 | 82 | 2 | 65 kA 3 s |
| MXM11013NS | MXM11013NS STEP file | 3 | 10 | 110 | 1 | 65 kA 3 s |
| MXM11023NS | MXM11023NS STEP file | 3 | 10 | 110 | 2 | 65 kA 3 s |
Termate Icw rating tested with supports at 300 mm centres
Dimensions
| Part Number | Length (L) | Width (W) | Height (H) | Slot Width (SW) | Base to Bar Height (H1) | Slot Centres (SC) | Fix Centres (FC) | Clearance (C) |
|---|---|---|---|---|---|---|---|---|
| MXM6013NS | 210 | 20 | 44.7 | 10.2 | 32 | 60 | 190 | 25.4 |
| MXM6513NS | 210 | 20 | 44.7 | 10.2 | 32 | 65 | 190 | 25.4 |
| MXM8213NS | 273 | 20 | 44.7 | 10.1 | 32 | 82 | 253 | 34.5 |
| MXM8223NS | 273 | 20 | 44.7 | 10.1 | 32 | 82 | 253 | 24.5 |
| MXM11013NS | 350 | 20 | 44.7 | 10.1 | 32 | 110 | 330 | 45 |
| MXM11023NS | 350 | 20 | 44.7 | 10.1 | 32 | 110 | 330 | 35 |
All dimensions are given in mm

Please refer to the “Spacer Selection Per Assembly” section for recommended spacers which must be ordered separately.
If using another method of fixing, please take into account the reduced creepage and clearance distances to the adjacent busbar.
* For the 2 bar version the dimension of the pip between the bars is the same as the slot width

- Material: Glass Reinforced Polyamide 6.6
- Conductor Temp.: 140 °C†
- Flammability: UL 94 V-0
- Glow Wire: 960 °C
- Equipment Voltage, Ue: 1000 V AC, 1500 V DC
- Insulation Voltage, Ui: 1000 V AC, 1500 V DC
- Impulse Voltage, Uimp: 12 kV
UL Recognised Component:
(Files E505645 (US) and E505645 (CA))
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085.
Reference
| Part Number | 3D Model | Number of Phases | Conductor Width (mm) | Phase Centres | Bars Per Phase | Termate Icw Rating |
|---|---|---|---|---|---|---|
| MX68224NS | MX68224NS STEP file | 4 | 6 | 82 | 2 | 65 kA 3 s |
| MXB6014NS | MXB6014NS STEP file | 4 | 6.3 | 60 | 1 | 50 kA 1 s |
| MXB6514NS | MXB6514NS STEP file | 4 | 6.3 | 65 | 1 | 50 kA 1 s |
| MXB6524NS | MXB6524NS STEP file | 4 | 6.3 | 65 | 2 | 65 kA 3 s |
Termate Icw rating tested with supports at 300 mm centres
Dimensions
| Part Number | Length (L) | Width (W) | Height (H) | Slot Width (SW) | Base to Bar Height (H1) | Slot Centres (SC) | Fix Centres (FC) | Clearance (C) |
|---|---|---|---|---|---|---|---|---|
| MX68224NS | 350 | 20 | 45.5 | 6.1 | 32 | 82 | 330 | 28 |
| MXB6014NS | 273 | 20 | 45.5 | 6.7 | 32 | 60 | 253 | 28.5 |
| MXB6514NS | 273 | 20 | 45.5 | 6.7 | 32 | 65 | 253 | 20.5 |
| MXB6524NS | 273 | 20 | 45.5 | 6.5 | 32 | 65 | 253 | 14 |
All dimensions are given in mm

Please refer to the “Spacer Selection Per Assembly” section for recommended spacers which must be ordered separately.
If using another method of fixing, please take into account the reduced creepage and clearance distances to the adjacent busbar.
* For the 2 bar version the dimension of the pip between the bars is the same as the slot width.

- Material: Glass Reinforced Polyamide 6.6
- Conductor Temp.: 140 °C†
- Flammability: UL 94 V-0
- Glow Wire: 960 °C
UL Recognised Component:
(Files E505645 (US) and E505645 (CA))
Type 1
Equipment Voltage, Ue: 1000 V AC, 1500 V DC
Insulation Voltage, Ui: 1000 V AC, 1500 V DC
Impulse Voltage, Uimp: 12 kV
Type 2
Equipment Voltage, Ue: 690 V AC, 690 V DC
Insulation Voltage, Ui: 690 V AC, 690 V DC
Impulse Voltage, Uimp: 8 kV
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085.
Reference
| Part Number | 3D Model | Number of Phases | Conductor Width (mm) | Phase Centres | Bars Per Phase | Termate Icw Rating | Type |
|---|---|---|---|---|---|---|---|
| MXM6014NS | MXM6014NS STEP file | 4 | 10 | 60 | 1 | 50 kA 1 s | 1 |
| MXM6514NS | MXM6514NS STEP file | 4 | 10 | 65 | 1 | 50 kA 3 s | 1 |
| MXM6524NS | MXM6524NS STEP file | 4 | 10 | 65 | 2 | 65 kA 3 s | 2 |
| MXHM7014NS | MXHM7014NS STEP file | 4 | 10 | 70 | 1 | 50 kA 3 s | 1 |
| MXM8214NS | MXM8214NS STEP file | 4 | 10 | 82 | 1 | 65 kA 3 s | 1 |
| MXM8224NS | MXM8224NS STEP file | 4 | 10 | 82 | 2 | 65 kA 3 s | 1 |
Termate Icw rating tested with supports at 300 mm centres
Dimensions
| Part Number | Length (L) | Width (W) | Height (H) | Slot Width (SW) | Base to Bar Height (H1) | Slot Centres (SC) | Fix Centres (FC) | Clearance (C) |
|---|---|---|---|---|---|---|---|---|
| MXM6014NS | 273 | 20 | 44.7 | 10.2 | 32 | 60 | 253 | 26.5 |
| MXM6514NS | 273 | 20 | 44.7 | 10.2 | 32 | 65 | 253 | 19 |
| MXM6524NS | 273 | 20 | 44.7 | 10.2 | 32 | 65 | 253 | 8.5 |
| MXHM7014NS | 350 | 20 | 44.7 | 10.1 | 32 | 70 | 330 | 37.5/62.5 |
| MXM8214NS | 350 | 20 | 44.7 | 10.1 | 32 | 82 | 330 | 32 |
| MXM8224NS | 350 | 20 | 44.7 | 10.1 | 32 | 82 | 330 | 32 |
All dimensions are given in mm

Please refer to the “Spacer Selection Per Assembly” section for recommended spacers which must be ordered separately.
If using another method of fixing, please take into account the reduced creepage and clearance distances to the adjacent busbar.
* For the 2 bar version the dimension of the pip between the bars is the same as the slot width.

- Material: Glass Reinforced Polyamide 6.6
- Conductor Temp.: 140 °C†
- Flammability: UL 94 V-0
- Glow Wire: 960 °C
- Equipment Voltage, Ue: 1000 V AC, 1500 V DC
- Insulation Voltage, Ui: 1000 V AC, 1500 V DC
- Impulse Voltage, Uimp: 12 kV
UL Recognised Component:
(Files E505645 (US) and E505645 (CA))
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085
Reference
| Part Number | 3D Model | Number of Phases | Conductor Width (mm) | Phase Centres | Bars Per Phase | Termate Icw Rating | Insulated |
|---|---|---|---|---|---|---|---|
| MX6I8224NS | MX6I8224NS STEP file | 4 | 6* | 82 | 2 | 50 kA 1 s | Yes |
| MXI6514NS | MXI6514NS STEP file | 4 | 6* | 65 | 1 | 50 kA 1 s | Yes |
| MXMI8214NS | MXMI8214NS STEP file | 4 | 10* | 82 | 1 | 50 kA 1 s | Yes |
* Conductor width shown is nominal copper width. Total width of conductor including insulation cannot exceed Slot Width (SW) shown below.
Termate Icw rating tested with supports at 300 mm centres
Dimensions
| Part Number | Length (L) | Width (W) | Height (H) | Slot Width (SW) | Base to Bar Height (H1) | Slot Centres (SC) | Fix Centres (FC) | Clearance (C) |
|---|---|---|---|---|---|---|---|---|
| MX6I8224NS | 350 | 20 | 45.5 | 7.5 | 32 | 82 | 330 | 27.5 |
| MXI6514NS | 273 | 20 | 45.5 | 7.5 | 32 | 65 | 253 | 20 |
| MXMI8214NS | 350 | 20 | 44.7 | 11 | 32 | 82 | 330 | 32 |
All dimensions are given in mm

Please refer to the “Spacer Selection Per Assembly” section for recommended spacers which must be ordered separately.
If using another method of fixing, please take into account the reduced creepage and clearance distances to the adjacent busbar.
*For the 2 bar version, the dimension of the pip between the bars is smaller than the slot width, this allows for the insulation material. The gap between the installed conductors is expected to be the same as the thickness of the conductors.

- Material: Glass Reinforced Polyamide 6.6
- Conductor Temp.: 140 °C†
- Flammability: UL 94 V-0
- Glow Wire: 960 °C
- Equipment Voltage, Ue: 1000 V AC, 1500 V DC
- Insulation Voltage, Ui: 1000 V AC, 1500 V DC
- Impulse Voltage, Uimp: 12 kV
UL Recognised Component:
(Files E505645 (US) and E505645 (CA))
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085.
Reference
| Part Number | 3D Model | Number of Phases | Conductor Width (mm) | Phase Centres | Bars Per Phase | Termate Icw Rating |
|---|---|---|---|---|---|---|
| MXMF407513NS | MXMF407513NS STEP file | 3 | 40 | 75 | 1 | 50 kA 1 s |
| MXMF507513NS | MXMF507513NS STEP file | 3 | 50 | 75 | 1 | 50 kA 1 s |
* Conductor width shown is nominal copper width. Total width of conductor including insulation cannot exceed Slot Width (SW) shown below.
Termate Icw rating tested with supports at 300 mm centres
Dimensions
| Part Number | Length (L) | Width (W) | Height (H) | Slot Width (SW) | Base to Bar Height (H1) | Slot Centres (SC) | Fix Centres (FC) | Clearance (C) |
|---|---|---|---|---|---|---|---|---|
| MXMF407513NS | 273 | 20 | 37 | 40.5 | 32 | 75 | 253 | 26 |
| MXMF507513NS | 273 | 20 | 37 | 40.5 | 32 | 75 | 253 | 21 |
All dimensions are given in mm

If using another method of fixing, please take into account the reduced creepage and clearance distances to the adjacent busbar.

- Material: Glass Reinforced Polyamide 6.6
- Conductor Temp: 140 °C†
- Flammability: UL 94 V-0
- Glow Wire: 960 °C
- Equipment Voltage, Ue: 1000 V AC, 1500 V DC
- Insulation Voltage, Ui: 1000 V AC, 1500 V DC
- Impulse Voltage, Uimp: 12 kV
UL Recognised Component:
(Files E505645 (US) and E505645 (CA))
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085.
Reference
| Part Number | 3D Model | Number of Phases | Conductor Width (mm) | Phase Centres | Bars Per Phase | Termate Icw Rating |
|---|---|---|---|---|---|---|
| MXMF407514NS | MXMF407514NS STEP file | 4 | 40 | 75 | 1 | 50 kA 1 s |
| MXMF507514NS | MXMF507514NS STEP file | 4 | 50 | 75 | 1 | 50 kA 1 s |
Termate Icw rating tested with supports at 300 mm centres
Dimensions
| Part Number | Length (L) | Width (W) | Height (H) | Slot Width (SW) | Base to Bar Height (H1) | Slot Centres (SC) | Fix Centres (FC) | Clearance (C) |
|---|---|---|---|---|---|---|---|---|
| MXMF407514NS | 350 | 20 | 37 | 40.5 | 32 | 75 | 330 | 27 |
| MXMF507514NS | 350 | 20 | 37 | 50.5 | 32 | 75 | 330 | 22 |
All dimensions are given in mm

If using another method of fixing, please take into account the reduced creepage and clearance distances to the adjacent busbar.

- Material: Polyamide 6
- Conductor Temp.: 140 °C†
- Flammability: UL 94 V-0
- Glow Wire: 960 °C
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085.
Number of Spacers per MX Support
| Conductor 25/25.4 mm | Conductor 30 mm | Conductor 50/50.8 mm | Conductor 60 mm | Conductor 75/76.2 mm | Conductor 80 mm | Conductor 100/101.6 mm |
|---|---|---|---|---|---|---|
| Not Required | 1 × MXS5 | 1 × CP25 | 1 × CP25 + 2 × MXS5 | 1 × CP50 | 1 × CP50 + 1 × MXS5 | 1 × CP50 + 1 × CP25 |
NOTE: Number of spacer is per support (2 supports are required per support assembly)
If the conductor being supported is greater than 100mm, additional spacers can be added as required using the principle as detailed in the above table. We do not recommend this installation method if the conductor exceeds 200mm high.
MXMF407513NS, MXMF507513NS, MXMF407514NS, and MXMF507514NS supports do not require spacers
Standard Support Arrangement

Flat Bar Support Arrangement

Termate is committed to the highest standard of customer focus and we have made every effort to maintain the accuracy and completeness of the information provided in this data.
Where improvements to our products affect their installation and usage we endeavour to contact any customers who may be affected.
Warranty as stated in our Terms and Conditions of Trading is void if any modification is made to the warranted product.