RMS Range
The RMS range of supports offer a solution for 3 × 10 mm, 3 × 10 mm insulated, and 6 × 5 mm conductors.
The RMS range of supports achieve fault ratings of up to 65 kA/1 s.
Their rail mounted design makes them easy to install, and their glass reinforced polyamide material makes them strong and lightweight.
- Up to 65 kA/1 s fault rating
- Rail mounted to give incredible installation versatility
- UL Recognised Component; File Number: E505645
RMS6-5 & RMS3-10
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085.
Fault Levels—Insulator tested at 300 mm spacing
Part Number | 3D Model | Conductors | Support Phase Centres | Termate Icw Rating | Duration |
---|---|---|---|---|---|
RMS6-5 | RMS6-5 STEP file | 6 × 50×5 | 110 | 50 kA | 1 s |
RMS3-10 | RMS3-10 STEP file | 1 × 50×10 | 110 | 50 kA | 3 s |
RMS3-10 | RMS3-10 STEP file | 2 × 50×10 | 110 | 50 kA | 3 s |
RMS3-10 | RMS3-10 STEP file | 3 × 50×10 | 130 | 65 kA | 1 s |
RMS3-10 | RMS3-10 STEP file | 3 × 50×10 | 130 | 50 kA | 3 s |
RMS3-10 | RMS3-10 STEP file | 3 × 75×10 | 130 | 65 kA | 1 s |
RMS3-10 | RMS3-10 STEP file | 3 × 75×10 | 130 | 50 kA | 3 s |
Insulated Copper RMSI3-10
† In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).
This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085
Fault Levels—Insulator tested at 300 mm spacing
Part Number | 3D Model | Conductors (Insulated) | Support Phase Centres | Termate Icw Rating | Duration |
---|---|---|---|---|---|
RMSI3-10 | RMSI3-10 STEP file | 1 × 50×10 | 110 | 50 kA | 1 s |
RMSI3-10 | RMSI3-10 STEP file | 2 × 50×10 | 110 | 50 kA | 1 s |
RMSI3-10 | RMSI3-10 STEP file | 3 × 50×10 | 130 | 50 kA | 1 s |
RMSI3-10 | RMSI3-10 STEP file | 3 × 75×10 | 130 | 65 kA | 1 s |
Mounting Rail
Slot dimensions should be 15×10 mm, tolerance of ±0.3 mm on both dimensions
RMS6-5
RMS3-10
RMSI3-10
Base Detail
Termate is committed to the highest standard of customer focus and we have made every effort to maintain the accuracy and completeness of the information provided in this data. Where improvements to our products affect their installation and usage we endeavour to contact any customers who may be affected.
Warranty as stated in our Terms and Conditions of Trading is void if any modification is made to the warranted product.