RMS Range

The RMS range of supports offer a solution for 3 × 10 mm, 3 × 10 mm insulated, and 6 × 5 mm conductors.

The RMS range of supports achieve fault ratings of up to 65 kA/1 s.

Their rail mounted design makes them easy to install, and their glass reinforced polyamide material makes them strong and lightweight.

  • Up to 65 kA/1 s fault rating
  • Rail mounted to give incredible installation versatility
  • UL Recognised Component; File Number: E505645
3D Rendering of RMS6-5 & RMS3-10 Busbar Supports

RMS6-5 & RMS3-10

  • Material: Glass Reinforced Polyamide 6.6
  • Conductor Temp.: 140 °C
  • Flammability: UL 94 V-0
  • Glow Wire: 960 °C
  • Equipment Voltage Ue: 1000 V AC, 1500 V DC
  • Insulation Voltage Ui: 1000 V AC, 1500 V DC
  • Impulse Voltage Uimp: 12 kV
  • UL Recognised Component: File number E505645

In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).

This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085.

Fault Levels—Insulator tested at 300 mm spacing

Part Number3D ModelConductorsSupport
Phase Centres
Termate Icw RatingDuration
RMS6-5RMS6-5 STEP file6 × 50×511050 kAs
RMS3-10RMS3-10 STEP file1 × 50×1011050 kAs
RMS3-10RMS3-10 STEP file2 × 50×1011050 kAs
RMS3-10RMS3-10 STEP file3 × 50×1013065 kAs
RMS3-10RMS3-10 STEP file3 × 50×1013050 kAs
RMS3-10RMS3-10 STEP file3 × 75×1013065 kAs
RMS3-10RMS3-10 STEP file3 × 75×1013050 kAs
3D Rendering of the RMSI3-10 Busbar Support

Insulated Copper RMSI3-10

  • Material: Glass Reinforced Polyamide 6.6
  • Conductor Temp.: 140 °C
  • Flammability: UL 94 V-0
  • Glow Wire: 960 °C
  • Equipment Voltage Ue: 1000 V AC, 1500 V DC
  • Insulation Voltage Ui: 1000 V AC, 1500 V DC
  • Impulse Voltage Uimp: 12 kV
  • UL Recognised Component: File number E505645

In line with the limits set out in IEC 61439, insulating components in contact with conductors may be required to continuously operate at an average of 140 °C (max. 145 °C).

This range of products meets the requirement, the material for them being assigned thermal class F established using methods similar to IEC 60085

Fault Levels—Insulator tested at 300 mm spacing

Part Number3D ModelConductors
(Insulated)
Support
Phase Centres
Termate Icw RatingDuration
RMSI3-10RMSI3-10 STEP file1 × 50×1011050 kAs
RMSI3-10RMSI3-10 STEP file2 × 50×1011050 kAs
RMSI3-10RMSI3-10 STEP file3 × 50×1013050 kAs
RMSI3-10RMSI3-10 STEP file3 × 75×1013065 kAs

Mounting Rail

Diagram showing the dimensions for a mounting rail for the RMS Busbar Supports

Slot dimensions should be 15×10 mm, tolerance of ±0.3 mm on both dimensions

RMS6-5

3D Rendering and diagram of dimensions for the RMS6-5 Busbar Support

RMS3-10

3D Rendering and diagram of dimensions for the RMS3-10 Busbar Support

RMSI3-10

3D Rendering and diagram of dimensions for the RMSI3-10 Busbar Support

Base Detail

Diagram showing the base dimensions for the RMS range of Busbar Supports

Termate is committed to the highest standard of customer focus and we have made every effort to maintain the accuracy and completeness of the information provided in this data. Where improvements to our products affect their installation and usage we endeavour to contact any customers who may be affected.

Warranty as stated in our Terms and Conditions of Trading is void if any modification is made to the warranted product.